    Small Industrial Power Supply Cooling Airflow Calculation and Fan Selection Example

    industrial-power-supply-airflow-calculation-worked-example
    By XQF FAN Engineering Team

    For an illustrative 500 W power supply operating at 90% efficiency, estimated heat loss is 55.6 W. Allowing a 10 K air-temperature rise produces a preliminary requirement of approximately 16.6 m³/h, or 9.8 CFM. The fan must then be selected at its intersection with the enclosure resistance curve—not by its free-air rating—and verified in a prototype.

    • Calculate loss from measured input and output power whenever possible.
    • Model restrictions before comparing candidate fan curves.
    • Treat every value below as illustrative until prototype testing confirms it.

    Define the thermal inputs

    At 500 W output and 90% efficiency, input is 500/0.90 = 555.6 W; estimated loss is 55.6 W. Record ambient temperature, altitude, component limits and the permitted air rise.

    Calculate preliminary airflow

    Use Q = P/(ρCpΔT). With ρ = 1.2 kg/m³, Cp = 1,005 J/(kg·K) and ΔT = 10 K, Q is 0.00461 m³/s, 16.6 m³/h or 9.8 CFM. These room-condition assumptions should be corrected for the application. NIST's Chemistry WebBook data for air supports using temperature-dependent heat-capacity data rather than treating air properties as universal constants.

    Estimate the system curve

    Include inlet openings, filters, grilles, heat sinks, wiring and outlet turns. For this example only, 20 Pa at 12 CFM gives Δp = 0.139Q² when Q is expressed in CFM. See the heat-load calculation method for the underlying workflow.

    Compare operating points

    Illustrative curve intersections are 11.5 CFM at 18 Pa for Candidate A and 13.5 CFM at 25 Pa for Candidate B. Both exceed 9.8 CFM, but B provides more restriction margin. Use verified curves and compare fan operating points, including voltage tolerance and installation effects.

    Validate the prototype

    Confirm hot-spot temperatures, minimum-voltage startup, airflow direction, obstruction sensitivity and acoustic performance. ISO's ISO 3744 overview defines an engineering method for sound-power measurement, showing why a supplier dB figure and an enclosure test are not automatically comparable.

    Is the calculated airflow the final fan rating?

    No. It is the required operating airflow after enclosure resistance is applied, not a free-air catalogue value.

    What should procurement send to a fan supplier?

    Provide voltage range, target operating point, space, connector, noise method, ambient conditions, control signals and life requirements.

    When is fan selection accepted?

    Accept it only after the prototype meets documented component-temperature, startup, acoustic and installation criteria at defined worst-case conditions.

    Reusable calculation and decision record

    Record Pout, efficiency or measured Pin, Ploss, ambient, allowable ΔT, air properties, system-curve evidence and candidate intersections. The complete industrial airflow workflow provides the broader selection sequence.

    Electrical, acoustic and installation constraints

    Before releasing Candidate B, verify rated and startup voltage, current, connector and polarity; fan envelope and guard clearance; tachometer or PWM needs; declared service-life conditions; and the exact acoustic test method. Request the supplier's curve, tolerances and test configuration rather than accepting one headline airflow value.

    Acceptance criteria

    Define pass limits before testing. Use component manufacturers' derated temperature limits, test maximum load and ambient, inspect recirculation, and repeat measurements with production-intent vents and filters. The calculation screens candidates; the instrumented prototype makes the final decision.

    Release time: 2026-11-28

    PV Inverter and Energy Storage Cooling Fan Selection

    How to Read Cooling Fan PQ Performance Curves Correctly

    Related blog
    2026-11-28
    PV Inverter and Energy Storage Cooling Fan Selection
    2026-11-28
    How to Read Cooling Fan PQ Performance Curves Correctly
    2026-11-28
    How to Calculate Industrial Equipment Heat Load and System Resistance

    +86 18820255739

    Rainie@xqffan.com

    ShenZhen,Guangdong Province

    Products
    • AC FAN

    • DC Fan

    • DC Blower Fan

      EC FAN

    Application

    • Industrial field

    • Communication field

    • Automobile industry

    • Medical Equipment​

    • Consumer Electronics​

    About Us

    Contact Us

    SiteMap

    Copyright © SZXQFFAN

    (472166)
    0