Welcome to XQF FAN official website

image English
  • image English
  • image Pусский
  • image 简体中文
  • image Türk dili
  • image Tiếng Việt
  • image Español
  • image العربية
  • image Français
  • image 日本語
  • image Deutsch
qr Code Url

Scan qrcode to view mobile website

szxqffan | xinqifeng | YH-XQF
    Home /Blog /工业设备散热风量计算与选型实操指南 /How to Read Cooling Fan PQ Performance Curves Correctly /

    How to Read Cooling Fan PQ Performance Curves Correctly

    how-to-read-a-cooling-fan-pq-performance-curve

    A cooling fan PQ curve plots airflow against static pressure. Maximum airflow occurs near zero pressure, while maximum static pressure occurs near zero airflow. Neither value represents normal installed performance. The expected working point is where the fan curve intersects the equipment system-resistance curve, subject to the stated voltage, air density, tolerance and test configuration.

    • Read airflow on one axis and static pressure on the other.

    • Do not treat free-air airflow as installed airflow.

    • Compare fans at the required system pressure.

    • Verify test conditions and performance tolerances.

    Identify the axes and test condition

    Confirm the airflow units, static-pressure units, rated voltage, speed and air condition. The International Organization for Standardization's ISO 5801 specifies laboratory methods for fan performance testing in standardized airways. This supports comparing curves only when their measurement conditions are compatible.

    Locate both endpoints

    The zero-pressure endpoint is free-air airflow. The zero-airflow endpoint is shutoff pressure. ANSI/AMCA Standard 210, jointly published by AMCA International and ASHRAE, defines standardized aerodynamic test methods; its scope supports treating airflow and pressure as paired test results rather than simultaneous maxima.

    Plot system resistance

    Use estimated pressure loss through filters, grilles, heat sinks and passages to build the system curve. See the enclosure pressure-loss method.

    Select at the intersection

    The intersection is the predicted operating point. Check that it meets thermal requirements with margin, then validate it in a prototype. An inverter fan selection example can connect this method to equipment-level decisions.

    Is maximum airflow the airflow delivered inside equipment?

    No. It is normally measured near zero static pressure. Installed airflow is lower when the enclosure creates resistance.

    Can two fans be compared by maximum airflow alone?

    No. Compare airflow at the project's required pressure and under equivalent voltage, speed, density and test conditions.

    What evidence should a buyer request?

    Request the complete curve, test method, sample configuration, voltage, speed, air condition, tolerances and confirmation that production units are controlled against the rated data.

    Nominal values versus installed performance

    A catalogue maximum is an endpoint, not a working-point guarantee. Use the complete airflow calculation workflow to connect heat load, required airflow and pressure margin.

    Environmental and tolerance effects

    The NASA Glenn Research Center's atmospheric density guidance shows that density depends on pressure and temperature. Because fan pressure performance depends on air density, buyers should document altitude and inlet temperature rather than assume a standard-density curve applies unchanged.

    Supplier verification checklist

    • Complete PQ curve and units
    • Test standard and airway configuration
    • Voltage, current, speed and density conditions
    • Curve tolerance and sample quantity
    • Filter ageing and installation-obstruction allowance

    AMCA International's Certified Ratings Program explains how ratings covered by its program are independently checked. Certification is not automatic for every fan, so purchasers should verify the exact model, rating scope and label instead of relying on a general supplier statement.

    Release time: 2026-11-28

    Small Industrial Power Supply Cooling Airflow Calculation and Fan Selection Example

    How to Calculate Industrial Equipment Heat Load and System Resistance

    Related blog
    2026-11-28
    PV Inverter and Energy Storage Cooling Fan Selection
    2026-11-28
    Small Industrial Power Supply Cooling Airflow Calculation and Fan Selection Example
    2026-11-28
    How to Calculate Industrial Equipment Heat Load and System Resistance

    +86 18820255739

    Rainie@xqffan.com

    ShenZhen,Guangdong Province

    Products
    • AC FAN

    • DC Fan

    • DC Blower Fan

      EC FAN

    Application

    • Industrial field

    • Communication field

    • Automobile industry

    • Medical Equipment​

    • Consumer Electronics​

    About Us

    Contact Us

    SiteMap

    Copyright © SZXQFFAN

    (472166)
    0